Transformer Oil Purification Plant CMM 0.6

    GlobeCore

    LEAVE A MESSAGE






    The GlobeCore CMM 0.6 – is designed for removal of free and dissolved water and mechanical contaminants from insulating oil, turbine oil, compressor oil, and lubricating oils.  Its compact design provides excellent mobility with an effective flow rate of 600 liters per hour (L.P.H.)  It is available in trolley or roadworthy trailer mounted, semi-automated, fully automated (PLC controlled) and explosion proof versions. Optional equipment includes moisture probes, flow meter with totalizer and 1 micron fine oil filter.

    myasorubkaGLOBECORE CMM 0.6 COMPONENT DESCRIPTION
    Vacuum System
    Rotary Vane Positive Displacement Pump
    Pumping Speed 25 m3/h
    Ultimate pressure 0.5 mbar
    Inlet and Outlet Oil Pumps
    Two Gear pumps with power consumption of 1.1 kW and capacity of 0.8 m3/h is  utilized to draw oil in and out of the vacuum system. Electric motors are protected by overloads.

    Vacuum Chamber and Oil Heater
    The Vacuum Chamber has an oil sprayer, provided to maximize exposure of oil to the effects of vacuum.
    A Coalescer Filter is installed between the Vacuum Chamber and the Vacuum Pump to ensure that no oil is drawn into the Vacuum Pump.
    15 kW Oil Heater with a low watt density heating elements (1.2 W/cm2) comes complete with thermometer and thermostat.  An Optional heater can be controlled by an electronic temperature controller or PLC.

    filters1Filters
    A Mesh Strainer is provided to remove large particles that could cause damage to the Inlet Pump.  A Coarse Filter for particles larger than 5 microns is installed at the entry port to the Vacuum Chamber.  Oil then receives its final treatment by passing through the Fine Filter designed to remove 99.9% of particles larger than 2 microns or with an optional 1 micron capability.

    Instrumentation and Controls
    The Control Panel is a dust proof enclosure to IP 54 and features the following elements:
    Manometers – are installed to monitor the state of Coarse and Fine Filters.
    A Vacuum Meter is provided to monitor vacuum level in the chamber.
    A Temperature controller (optional) – receives  a data input from the temperature sensor and is  connected to a control element of the heater.
    Power and Heating Indicators and Switches, Oil Pump Switches and PLC with Mnemonic Diagram (optional).
    Emergency Stop Button – is provided for safe shut down of the plant in case of emergency.

    equipOPTIONAL EQUIPMENT
    Moisture Probe
    The transmitter provides on-line transformer oil measurement of both the temperature and moisture content.  The unit comes complete with a display showing the level of moisture in a “ppm” readout.
    Flowmeter
    The “Influx Flotrack” flow meter gives a reading in m3/h and a totalizer shows the amount of total flow that has passed through the meter in a given amount of time.

    auto

                 1                               2                               3

    1 – manual, 2 – semi automated. 3 – fully automated

    GlobeCore CMM 0.6 Flow Diagram

    Flow Diagram

    P1P2– gear pumps; PV – vacuum pump; МB– vacuum meter; М1, М2– manometers; F1– coarse filter; FP2– fine filter; PF– mesh filter;   FA1, FA2 – coalescer filter KO– return valve  ; K1 – inlet valve; K2 – three way valve; K3 – air valve; K4, K5, K8, K10 – drain valves; К6, K7– by-pass valve

    No. Parameter Value
    1 Efficiency, m3/h (gpm) 0.6 (2.6)
    2 Power supply (50Hz AC, V) 380*
    3 Rated input power, kW 14
    4 Filtration degree, micron 5
    5 Moisture content, ppm 10 ppm, or 5 ppm, or 5 ppm+ (optional)
    6 Oil purity level after processing (as per ISO 4406) -/14/12
    7 Oil breakdown voltage, at least, kV 60**
    8 Outer dimensions (excl. hoses), mm (in), max
    — length 750 (29.5)
    — width 525 (20.7)
    — height 1,450 (57.1)
    9 Weight (without oil), kg (lbs), max 230 (507)

    * – any voltage available at the customer’s request

    ** – provided that processable oil has not been in use

    You can purchase the CMM-0.6 degassing unit right now by contacting one of our relationship managers on the contact list.

    In order to change the default parameters depending on specific needs, the Customer shall fill out a questionnaire, wherein the necessary technical requirements should be listed.

    • The unit is mobile and has a compact size;
    • ease in maintenance and operation;
    • protection against oil spillage and foaming;
    • silent operation;
    • provide top level of oil degassing and filtration;
    • can be connected to the power source via an ordinary outlet;
    • improves the reliability of oil-filled equipment.